Call a Specialist Today! 833-335-0427

Eaton FERRUPS 60 Hz Rackmount Technical Specifications
Uninterruptible Power Supply

Eaton FERRUPS RM
Model FER3.1 (3.1 kVA/2.2 kW)

Eaton FERRUPS 60 Hz Rackmount Technical Specifications
General
Topology Ferroresonant
Part Number RI000JB3A0A0A0B
Color Beige with blue highlights
Rating (VA/Watts) 3100/2200
Dimensions (H x W x D, inches) 9.75 x 16 x 26.25
Weight (lbs) 238
Warranty Two-year factory warranty
Electrical Input
Connection L5-30P
L5-30P
Nominal Voltage 120 VAC
Frequency 60 Hz
Breaker Ratings 20
Generator Compatability Yes
Electrical Output
Output Receptacles (6) 5-15R
5-15R
On Utility Voltage Regulation ±3% for input voltages +15%, -20% of nominal. +5%,-8.3% for any line, load or battery condition.
On Battery Voltage Regulation ±3% for input voltages +15%, -20% of nominal. +5%,-8.3% for any line, load or battery condition.
Voltage Wave Shape (On Battery) Sine Wave
Transfer Time 0 ms
Battery
Battery Runtime 100%/50% load typical runtime: 850 VA: 11/28 min. 1.15 kVA: 19/49 min. 1.4 kVA: 14/36 min. 1.8 kVA: 31/73 min. 2.1 kVA: 24/58 min. 3.1 kVA: 14/35 min. 4.3 kVA: 26/61 min. 7 kVA: 12/33 min.
Communications
Communication Ports DB25 communication port with RS-232 serial communications, alarm and inverter contact closures, and EPO shutdown.
Environmental & Standards
Heat Dissipation (BTU) 742
Audible Noise 850VA: 48 dBA 1.15 - 2.1 kVA: 50 dBA 3.1 kVA: 51 dBA 4.3 kVA: 50 dBA 7 kVA: 52 dBA
Operating Temperature 0°C to 40°C
Lightning / Surge Protection 2000:1 spike attenuation using C62.41 and C62.45 Category A and Category B tests.
Storage Temperature -20° to +60° C (-20° to +40° C if battery not removed)
Relative Humidity 5 to 95% without condensation