Eaton BladeUPS Power System Technical Specs
Uninterruptible Power Supply
![]()
| General Characteristics | |
| Power Rating | 12 kW per UPS Module |
| Efficiency | Up to 98% |
|
System
efficiency (%) Load (%)
Mouseover graph for detailed efficiency values
* These efficiencies are for guidance only. Actual unit and system efficiencies will vary based on site design/conditions and environmental parameters. |
|
| Heat Dissipation | 371W/1266 BTU/hr. at 100% rated load |
| Cooling | Fan cooled, temperature microprocessor monitored; front air entry, rear exhaust |
| Audible Noise, Normal Operation | <60 dBA at 1 meter |
| Altitude before derating | 1000 meters (3300 ft. ASL) |
| Input Characteristics | |
| Input Voltage | 208 Vac and 400 Vac models |
| Voltage Range | 208V model: 180 to 265 Vac 400V model: 311 to 519 Vac |
| Frequency Range | 50 or 60 Hz, ±5 Hz |
| Input Current Distortion | <5% with IT loads (PFC power supplies) |
| Input Power Factor | >0.99 with IT loads (PFC power supplies) |
| Inrush Current | Load dependent |
| Input Requirements | Three-phase, four-wire + ground |
| Bypass Source | Same as input, (single feed) |
| Generator Compatibility | Fast sync slew rate for optimum generator synchronization |
| Output Characteristics | |
| Rated Output Voltage | 208V model: 180 to 225 Vac, Ph to Ph 400V model: 180 to 240 Vac, Ph to N |
| Output Configuration | Three-phase, four-wire + ground |
| Output Frequency (nominal) | 50 or 60 Hz auto-detection on startup |
| Frequency Regulation | 0.1 Hz free running |
| Load Power Factor Range | Lagging: 0.7 Leading: 0.9 |
| Total Output Voltage Distortion |
<3% with IT loads (PFC power supplies) <5% non-linear or non-PFC power supplies |
| Battery Characteristics | |
| Battery Type | VRLA - AGM |
| Battery Runtime (Internal) | 13 minutes at 50% load 4.8 minutes at 100% load |
| Battery String Voltage | 240 Vdc |
| Battery Test | Automatic battery test standard (remote scheduling capable). Manual battery test from front display |
| Battery Recharge Profile | ABM three-stage charging technology |
| Battery Cut-off Voltage | Variable from 1.67 VPC at <5 min. runtime to 1.75 VPC at >90 min. runtime |
| Battery Low Condition | Announced with alarm |
| Extended Battery Capability | Yes, add up to four additional 3U battery enclosures (~34 min at 100% load, >1 hour at 50% load) |
| Physical Characteristics | |
| Dimensions H x W x D, in (mm) UPS EBM |
br> 10.3 (6U) x 17.4 x 26.0 (267 x 442 x 660) 5.2 (3U) x 17.2 x 26.0 (132 x 437 x 660) |
| Note: Total Chassis Weight without batteries or electronics Total Chassis Weight with batteries or electronics |
br>
100 lb. (46 kg) 307 lb. (140 kg) |
| Total UPS Weight without Batteries | 135 lb. (61 kg) |
| Total UPS Weight with Batteries | 307 lb. (140 kg) |
| EBM Weight | 170 lb. (77 kg) |
| Communications and User Interface | |
| Software Compatibility | UPS ships with Software Suite CD containing Intelligent Power Manager supervisory software and NetWatch protection software |
| X-Slot Bays | Two available for the cards listed below |
| Control panel LCD | Two lines by 20 characters Four menu-driven interface buttons Four status at a glance LEDs |
| Multi Language | English standard; 20 languages available |
| Configuration Changes | User capable, firmware auto configures |
| Dry Contact Inputs | Two, user-configurable |
| Dry Contact Outputs | One, user-configurable |
| Service | |
| Installation | User capable, located in the IT racks |
| Preventative Maintenance | User capable, optional factory service available |
| Corrective Maintenance | User capable, optional factory service available |
| Serviceability Features | Hot-swappable batteries Hot-swappable electronics module Automated internal maintenance bypass Auto-configure firmware Flash firmware upgradeable |
| Certifications | |
| Safety | 208V model: UL1778, cUL 400V model: CE |
| EMI | 208V model: FCC Part15 Class A 400V model: EN62040-2 Class A |
| Surge Protection | ANSI C62.41, Cat B-3 |
| Hazardous materials (RoHS) | EU Directive 2002/95/EC Category 3 (5 of 6) |
| Warranty | |
| Standard | 18 months from date of shipment |
| Warranty Repair | Factory depot repair or replace |
| Service Support Agreements2 | |
| Depot | PowerTrust Express |
| On-site 5x8 | PowerTrust Value |
| On-site 7x24 | PowerTrust eight-, six- or two-hour response |
| Options and Accessories | |
| Detachable input cord | |
| Detachable input/output cord assembly | |
| Detachable paralleling cord assembly | |
| Extended Battery Modules (EBMs) | |
| 3U output sub-distribution module | |
| 0U to 3U rack power strips | |
| 60 kW BladeUPS Parallel Bar, Top Entry, Bottom Entry & 4-high versions | |
| Four-post rail kit | |
| Environmental Monitoring Probe (EMP) for temperature and humidity monitoring | |
| 3U Maintenance Bypass Module | |
| External Battery Interconnect for use with 400V models | |
| Optional X-Slot Communication Cards | |
| Application | Card |
| Web/SNMP | Connect UPS card |
| Modbus RTU | Modbus Card |
| Modbus TCP/IP | PowerXpert Gateway UPS card |
| IBM eServer (i5, iSeries, or AS/400) |
Relay Interface Card |
| N/O, N/C (dry contacts |
Industrial relay card |
| Parallel | Powerware Hot Sync CAN Bridge card |
1. Due to continuing product improvement programs, specifications are subject to change without notice.
2. eNotify Remote Monitoring and 7x24 technical support included.