Eaton 9P X5KP1 Tower UPS Technical Specifications
Reliable, versatile and efficient backup power for IT equipment, including Cisco switches and servers

The 9PX has the versatility to meet the demands of a wide array of IT applications.
| Eaton 9P X5KP1 Tower UPS Technical Specifications | |
|---|---|
| General | |
| Topology | Double-conversion online |
| Configuration | Rack/Tower |
| Catalog Number | 9PX5KP1 |
| Color | Black and silver |
| Rating (VA/Watts) | 5000/4500 |
| Diagnostics | Full system self-test at power up |
| UPS Bypass | Internal to PPDM |
| Dimensions (H x W x D, inches) | 10.2 (6U) x 17.3 x 28.4 |
| Dimensions (H x W x D, mm) | 259 (6U) x 439 x 721 |
| Weight (kg) | 92 |
| Weight (lbs) | 203 |
| Warranty | 2 years |
| Rail Kit Included | 4-post rail kit and tower pedastals included |
| Remote Emergency Power off (REPO) | ROO/RPO: Rear deck emergency stop connectors (for remote on/off and power off) |
| Contents (Ships with the following items) |
9PX5K 5kVA UPS 9PXPPDM1 PowerPass Distribution Module Network-MS Web/SNMP card 4-post rail kit User manual Quick start guide Tower pedestals Intelligent Power Software Suite CD RS-232 serial cable USB cable Cable gland for hardwire connection Phillips head screw driver |
| Electrical Input | |
| Connection | (1) NEMA L6-30P![]() |
| Input Cord | 6 feet (1.8 meters) |
| Input Voltage Range | Full load: 176-276V, Derating: 100-276V |
| Nominal Voltage | 120/208V default (200/208/220/230/240V) |
| Frequency | 50/60 Hz (auto-sensing) |
| Frequency Range | 60 Hz: 50–70 Hz, 50 Hz: 40–60 Hz |
| Input Power Factor | >99 |
| Input Current Distortion | <5% |
| Electrical Output | |
| Nominal Voltage | 120/240V default (200/208/220/230/240V) |
| Output voltage regulation | ±1% steady-state |
| Voltage THD | <2% for linear loads |
| Output Receptacles | (6) NEMA 5-20R![]() (1) NEMA L6-30R ![]() (1) NEMA L14-30R ![]() |
| Power Factor | 0.9 |
| Transfer Time | 0 ms |
| Circuit Breaker | (1) 30A for L6-30R; (1) 30A for L14-30R; (2) 20A for 5-20R |
| Optional Extended Battery Module | 9PXEBM180RT |
| Battery Description | Sealed, lead-acid; maintenance free |
| Maximum number of extended battery modules (EBM) | Add up to 4 extended battery modules (EBM) |
| Battery Management | ABM technology; 3-stage charging extends battery service life by 50% and provides advance warning for battery replacement |
| Battery Replacement | Hot-swappable internal batteries and extended battery modules (EBMs) |
| Start on Battery | Cold-start enabled; first cold start is always forbidden |
| Communications | |
| User Interface | Graphical display. UPS status in a single view. |
| LEDs | 4 status-indicating LEDs |
| Communication Ports | RS-232 (RJ45) ports; USB port as standard (HID). 6-foot RS-232 and USB cables included |
| Communications Card Slots | Network Card-MS included |
| Power Management Software | Eaton Intelligent Power Software Suite CD (included) |
| Environmental & Standards | |
| RoHS Compliance | Yes |
| Surge Protection | IEEE ANSI C62.41 Cat B2 |
| Audible Noise | <45 dB at 1 meter |
| Operating Temperature | 0 to 40°C (32°F to 104°F) |
| Safety markings | CE / cULus / NOM |
| Safety markings | UL, cUL |
| EMC Markings | IEC 62040-2:2006 Cat C2 / CISPR22 Class A / FCC part 15 Class A |
| Storage Temperature | 0 to 35°C (32°F to 95°F); without batteries: -15 to 60°C (5°F to 140°F) |
| Relative Humidity | 0 to 95% |
| Altitude | <1,000 meters for nominal power; 10% power derating every 1000 meters (up to 3000 meters) |