Call a Specialist Today! 833-335-0427

Eaton 9PX 11KTF11 Rack/Tower UPS Technical Specifications
Reliable, versatile and efficient backup power for IT equipment, including Cisco switches and servers

8ktf5
11,000 VA/10,000W, 120/208V

The 9PX has the versatility to meet the demands of a wide array of IT applications.

Eaton 9PX 11KTF11 Rack/Tower UPS Technical Specifications
General
Topology Double-conversion online
Configuration Rack/Tower
Catalog Number 9PX11KTF11
Color Black and silver
Rating (VA/Watts) 11000/10000
Diagnostics Full system self-test at power up
Efficiency 94% with resistive load

Mouseover graph for detailed efficiency values
UPS Bypass Yes, ships with MBP11K208
Dimensions (H x W x D, inches) 15.3 (9U) x 17.3 x 27.6
Dimensions (H x W x D, mm) 389 (9U) x 439 x 701
Weight (kg) 171
Weight (lbs) 377
Warranty 2 Years
Rail Kit Included 4-post rail kit and tower pedastals included
Remote Emergency Power off (REPO) ROO/RPO: Rear deck emergency stop connectors (for remote on/off and power off)
Contents
(Ships with the following items)
9PX11KPM 11 kVA 3U UPS power module
9PXEBM240RT 3U extended battery module
9PXTFMR11 11K 120V Stepdown Transformer
Network-MS Web/SNMP card
4-post rail kit
User manual
Quick start guide
Tower pedestals
Intelligent Power Software Suite CD
RS-232 serial cable
USB cable
Cable gland for hardwire connection
Phillips head screw driver
Electrical Input
Connection Hardwired
hardwired
Input Cord None; hardwired
Input Voltage Range Full load: 176-276V, Derating: 100-276V
Nominal Voltage 208V default (200/208/220/230/240/250V)
Frequency 50/60 Hz
Frequency Range 60 Hz: 50–70 Hz, 50 Hz: 40–60 Hz
Input Power Factor >99
Input Power Factor <5%
Electrical Output
Nominal Voltage 120/240V default (200/208/220/230/240/250V)
Output voltage regulation ±1% steady-state
Voltage THD <2% for linear loads
Output Receptacles (8) NEMA 5-20R
20r
(2) NEMA L14-30R
30r Hardwired
hardwired
Power Factor 0.9+
Transfer Time 0 ms
Circuit Breaker (2) 30A for L14-30R; (2) 20A for 5-20R
Battery
 

Runtime
(minutes)
Load (watts)

Show:

Mouseover graph for detailed runtime values


Battery runtimes are approximate and may vary with equipment, configuration, battery age, temperature, etc.

Optional Extended Battery Module 9PXEBM240RT
Battery Description Sealed, lead-acid; maintenance free
Maximum number of extended battery modules (EBM) Add up to 5 extended battery modules (EBM) with UPS; add up to 12 EBMs with SC240RT supercharger module
Battery Management ABM technology; 3-stage charging extends battery service life by 50% and provides advance warning for battery replacement
Battery Replacement Hot-swappable extended battery modules (EBMs); no internal batteries in UPS module
Start On Battery Cold-start enabled; first cold start is always forbidden
Communications
User Interface Graphical display. UPS status in a single view.
LEDs 4 status-indicating LEDs
Communication Ports RS-232 (RJ45) ports; USB port as standard (HID). 6-foot RS-232 and USB cables included
Communications Card Slots Network Card-MS included
Power Management Software Eaton Intelligent Power Software Suite CD (included)
Environmental & Standards
RoHS Compliance Yes
Surge Protection IEEE ANSI C62.41 Cat B2
Audible Noise <45 dB at 1 meter
Operating Temperature 0 to 40°C (32°F to 104°F)
Safety markings CE / cULus / NOM
EMC Markings IEC 62040-2:2006 Cat C2 / CISPR22 Class A / FCC part 15 Class A
Storage Temperature 0 to 35°C (32°F to 95°F); without batteries: -15 to 60°C (5°F to 140°F)
Relative Humidity 0 to 95%
Altitude <1,000 meters for nominal power; 10% power derating every 1000 meters (up to 3000 meters)