Call a Specialist Today! 833-335-0427

Eaton 9390IT technical specifications
Uninterruptible Power Supply

Eaton 9E
Eaton 9390IT UPS 40 kVA 480/480 V

Eaton 9E 60 KVA UPS with Batteries and Bypass System
General
Part Number TA04A2001150010
Rating (VA/Watts) 40000/36000
Dimensions (H x W x D, inches) 73.7"H x 27.9"W x 31"D
Warranty One-year standard warranty
Parallel Capability 4 modules with tie cabinet
Electrical Input
Connection Hardwired - see manual for terminal block layout
Hardwired - example layout only
Voltage Range +10% / -15%³
Frequency Range 55-65 Hz
Input Power Factor 0.99 (min)
Input Current Distortion 4.5% (no input filter required)
Soft Start Capability Yes
Internal Backfeed Protection Yes
Broadcast Global Support Yes
Electrical Output
Power Rating (VA) 40 kVA
Power Rating (Watts) 36 kW
Load Power Factor Range Down to 0.9 pf leading without de-rating
Voltage THD 2% (100% linear load); < 5% (non-linear load)
Output Receptacles Hardwired - see manual for terminal block layout
Hardwired - example layout only
Regulation ±1%
Inverter PWM with IGBT Switching
Battery

Runtime
(minutes)
Load (watts)
Mouseover graph for detailed runtime values


Battery runtimes are approximate and may vary with equipment, configuration, battery age, temperature, etc.
Battery Type VRLA, 12V, 9Ah
Battery Voltage 480V
Temperature Compensation Optional
Charger Advanced battery management
Environmental & Standards
Surge Protection ANSI C62, 41 Cat, A&B
Heat Dissipation (BTU) 21.9 @ full load
Audible Noise 65dBA @ 1 meter
Safety markings UL1778, cUL
EMC Markings IEC62040-2 EN50091 Class A (restricted access)
Altitude 2000m at 40ºC, 104ºF
1. Due to continuing improvements, specifications are subject to change without notice.
2. At full load without battery discharge.
3. Output transformers are required if the desired output voltage is not the same as the input voltage.
4. 600V applications require an output transformer.