Eaton 9355 UPS 20 and 30 kVA Technical Specs
Uninterruptible Power Supply
Battery Runtimes
Model Selection Guide
Options
X-Slot Connectivity Options
| Technical Specifications for 20 and 30 kVA1 | |
|---|---|
| Power | |
| Ratings (kVA/Watts) | 20 kVA/18 kW and 30 kVA/27 kW at 0.9 power factor |
| Topology | Double conversion |
| Electrical Input | |
| Nominal input voltage | 208V/120V, 220V/127V +10, -15% 480V/277V, 600V (480+600 with transformer) 400V models also available |
| Operating frequency | 50/60 Hz (45 to 65 Hz) |
| Input power factor | 0.99 typical |
| Input current distortion | 5% THD |
| Electrical Output | |
| Nominal output voltage | 208/120, 220/120 Vac |
| Output voltage regulation | ±1% static; ±4% dynamic with 100% step load recovery within 1 ms response time |
| Efficiency | 91%, typical |
| Heat dissipation (BTU/hr) | 20 kVA models 6,762 @ 208V and 220V input 10,450 @ 480V and 600V (with input isolation transformer) 30 kVA models: 9,220 @ 208V and 220V input 13,831 @ 480V and 600V (with input isolation transformer) |
| Battery | |
| Batterytype | 9 Ah, sealed, lead-acid, maintenance-free |
| Battery runtime | See battery backup time chart |
| Batteryreplacement | Field-replaceable |
| Charger | Default is 8A |
| General | |
| Diagnostics | Full system self-test at startup |
| UPS bypass | Automatic on overload or UPS failure |
| Parallel for redundancy | Yes, using Powerware Hot Sync technology and capacity |
| Dimensionsand weights | See model selection table |
| Overload | 150% for 5 sec / 125% for 1 min (online), 110% for 10 min |
| Communications | |
| LCD display | Graphical LCD with blue backlight |
| LEDs | (4) LEDs fornotice and alarm |
| Audiblealarms | Yes |
| Communication ports | (1) RS-232,(1) relay contact, (1) REPO, (2) environmental input |
| Communication slot | (2) X-Slot communication bays |
| Power management software | BundledSoftware Suite CD |
| Environmental | |
| Operating temperature | 50–104ºF (10–40ºC), 45ºC with 7.5% derating; Optimal battery performance: 77ºF (25ºC) |
| Storage temperature | 32–77ºF (0–25ºC); Recommended battery storage: 59–77ºF (15–25ºC) |
| Relativehumidity | 0–95%, non-condensing |
| Audiblenoise | 58 dBA at 1 meter depending on load |
| Altitude | 3000m |
| Certifications | |
| Safety certifications | IEC 62040-1-1, IEC 60950, EN 62040-1-1, UL 1778, NOM-0190SCP8-1993 |
| EMCcompliance | EN 50091-2 Class A |
| Quality | ISO 9001: 2000 and ISO14001:1996 |
| Markings | UL, cUL, NOM-NYCE |
1. Due to continuous product improvements, program specifications are subject to change without notice.
Note: Backup times are approximate and may vary with equipment, configuration, battery age, temperature etc.
1. 50/60 Hz auto-sensing.
2. An input neutral is required for all configurations unless the input isolation transformer is used. For parallel systems, change the fifth CTO digit to a 2 and include parallel tie cabinet.
3. All models include internal batteries.
4. Add 50 lb. to determine shipping weight.
5. Contains on-board maintenance bypass.
6. With isolation transformer.
7. 220V units are wye connected 220/127V input and 220/127V output, three-phase, four-wire plus ground
1. 400A Bus, 200A Neutral, (1) 350A MBP and (4) 110A MIS.
2. Requires Industrial Relay and Display Card. See X-Slot Connectivity Options table
3. Add 40 lb. for shipping weight of panels and 50 lb. for panels with panelboard provisions.
1. The UPS has two X-Slots. One card can be factory installed while the second X-Slot card can be purchased separately.
2. 5A @ 250V. Provides (4) form-C relay contacts for integrating UPS alarms into security and alarm systems. Also provides signal information for the Remote Monitor Display Panel (part number 103002687-001).