Eaton BladeUPS Power System Technical Specs
Uninterruptible Power Supply
General Characteristics | |
Power Rating | 12 kW per UPS Module |
Efficiency | Up to 98% |
System
efficiency (%) Load (%)
Mouseover graph for detailed efficiency values
* These efficiencies are for guidance only. Actual unit and system efficiencies will vary based on site design/conditions and environmental parameters. |
|
Heat Dissipation | 371W/1266 BTU/hr. at 100% rated load |
Cooling | Fan cooled, temperature microprocessor monitored; front air entry, rear exhaust |
Audible Noise, Normal Operation | <60 dBA at 1 meter |
Altitude before derating | 1000 meters (3300 ft. ASL) |
Input Characteristics | |
Input Voltage | 208 Vac and 400 Vac models |
Voltage Range | 208V model: 180 to 265 Vac 400V model: 311 to 519 Vac |
Frequency Range | 50 or 60 Hz, ±5 Hz |
Input Current Distortion | <5% with IT loads (PFC power supplies) |
Input Power Factor | >0.99 with IT loads (PFC power supplies) |
Inrush Current | Load dependent |
Input Requirements | Three-phase, four-wire + ground |
Bypass Source | Same as input, (single feed) |
Generator Compatibility | Fast sync slew rate for optimum generator synchronization |
Output Characteristics | |
Rated Output Voltage | 208V model: 180 to 225 Vac, Ph to Ph 400V model: 180 to 240 Vac, Ph to N |
Output Configuration | Three-phase, four-wire + ground |
Output Frequency (nominal) | 50 or 60 Hz auto-detection on startup |
Frequency Regulation | 0.1 Hz free running |
Load Power Factor Range | Lagging: 0.7 Leading: 0.9 |
Total Output Voltage Distortion |
<3% with IT loads (PFC power supplies) <5% non-linear or non-PFC power supplies |
Battery Characteristics | |
Battery Type | VRLA - AGM |
Battery Runtime (Internal) | 13 minutes at 50% load 4.8 minutes at 100% load |
Battery String Voltage | 240 Vdc |
Battery Test | Automatic battery test standard (remote scheduling capable). Manual battery test from front display |
Battery Recharge Profile | ABM three-stage charging technology |
Battery Cut-off Voltage | Variable from 1.67 VPC at <5 min. runtime to 1.75 VPC at >90 min. runtime |
Battery Low Condition | Announced with alarm |
Extended Battery Capability | Yes, add up to four additional 3U battery enclosures (~34 min at 100% load, >1 hour at 50% load) |
Physical Characteristics | |
Dimensions H x W x D, in (mm) UPS EBM |
br> 10.3 (6U) x 17.4 x 26.0 (267 x 442 x 660) 5.2 (3U) x 17.2 x 26.0 (132 x 437 x 660) |
Note: Total Chassis Weight without batteries or electronics Total Chassis Weight with batteries or electronics |
br>
100 lb. (46 kg) 307 lb. (140 kg) |
Total UPS Weight without Batteries | 135 lb. (61 kg) |
Total UPS Weight with Batteries | 307 lb. (140 kg) |
EBM Weight | 170 lb. (77 kg) |
Communications and User Interface | |
Software Compatibility | UPS ships with Software Suite CD containing Intelligent Power Manager supervisory software and NetWatch protection software |
X-Slot Bays | Two available for the cards listed below |
Control panel LCD | Two lines by 20 characters Four menu-driven interface buttons Four status at a glance LEDs |
Multi Language | English standard; 20 languages available |
Configuration Changes | User capable, firmware auto configures |
Dry Contact Inputs | Two, user-configurable |
Dry Contact Outputs | One, user-configurable |
Service | |
Installation | User capable, located in the IT racks |
Preventative Maintenance | User capable, optional factory service available |
Corrective Maintenance | User capable, optional factory service available |
Serviceability Features | Hot-swappable batteries Hot-swappable electronics module Automated internal maintenance bypass Auto-configure firmware Flash firmware upgradeable |
Certifications | |
Safety | 208V model: UL1778, cUL 400V model: CE |
EMI | 208V model: FCC Part15 Class A 400V model: EN62040-2 Class A |
Surge Protection | ANSI C62.41, Cat B-3 |
Hazardous materials (RoHS) | EU Directive 2002/95/EC Category 3 (5 of 6) |
Warranty | |
Standard | 18 months from date of shipment |
Warranty Repair | Factory depot repair or replace |
Service Support Agreements2 | |
Depot | PowerTrust Express |
On-site 5x8 | PowerTrust Value |
On-site 7x24 | PowerTrust eight-, six- or two-hour response |
Options and Accessories | |
Detachable input cord | |
Detachable input/output cord assembly | |
Detachable paralleling cord assembly | |
Extended Battery Modules (EBMs) | |
3U output sub-distribution module | |
0U to 3U rack power strips | |
60 kW BladeUPS Parallel Bar, Top Entry, Bottom Entry & 4-high versions | |
Four-post rail kit | |
Environmental Monitoring Probe (EMP) for temperature and humidity monitoring | |
3U Maintenance Bypass Module | |
External Battery Interconnect for use with 400V models | |
Optional X-Slot Communication Cards | |
Application | Card |
Web/SNMP | Connect UPS card |
Modbus RTU | Modbus Card |
Modbus TCP/IP | PowerXpert Gateway UPS card |
IBM eServer (i5, iSeries, or AS/400) |
Relay Interface Card |
N/O, N/C (dry contacts |
Industrial relay card |
Parallel | Powerware Hot Sync CAN Bridge card |
1. Due to continuing product improvement programs, specifications are subject to change without notice.
2. eNotify Remote Monitoring and 7x24 technical support included.