Eaton 5P 2200 Tower UPS Technical Specifications
Enterprise class battery backup in a space-saving tower design for network closets and computer rooms
The Eaton 5P tower provides premium protection while conserving value space in multiple, slim tower designs.
Eaton 5P 2200 Tower UPS Technical Specifications | |
---|---|
General | |
Topology | Line-interactive |
Configuration | Tower |
Catalog Number | 5P2200 |
Color | Black |
Rating (VA/Watts) | 1950/1920 |
Diagnostics | Full system self-test at power up |
Efficiency | up to 99%
Mouseover graph for detailed efficiency values |
Dimensions (H x W x D, inches) | 17.4 x 3.4 x 20.6 |
Dimensions (H x W x D, mm) | 441 x 86 x 522 |
Weight (kg) | 30 |
Weight (lbs) | 65 |
Warranty | 3 years on electronics, 3 years on batteries with registration |
Rail Kit Included | Tower stand included |
Contents (Ships with the following items) |
5P2200 User Manual CD Intelligent Power Software Suite CD Quick start guide USB cable RS-232 serial cable Phillips head screw driver |
Electrical Input | |
Connection | 5-20P![]() |
Input Cord | 8 feet |
Input Voltage Range | 89–151 Vac (adjustable to 70–153 Vac) |
Nominal Voltage | 120 Vac (adjustable to 100/120/127 Vac) |
Frequency | 50/60 Hz (auto-sensing) |
Frequency Range | 47–70 Hz (50 Hz system), 56.5–70 Hz (60 Hz system), 40 Hz in low-sensitivity mode |
Input Power Factor | 0.98 |
Electrical Output | |
Output Receptacles | (8) 5-20R![]() |
On Utility Voltage Regulation | 102–132 Vac |
On Battery Voltage Regulation | -10%, +6% of nominal |
Output Frequency | 50/60 Hz ±0.1 % (autosensing) |
Output Frequency | 1–4 ms typical |
Load Segments | Group 1: (2) 5-20R outlets; Group 2: (2) 5-20R outlets |
Battery | |
Runtime
(minutes) Load (watts)
Mouseover graph for detailed runtime values
Battery runtimes are approximate and may vary with equipment, configuration, battery age, temperature, etc.
|
|
Battery Management | ABM® technology and temperature-compensated charging method (user selectable), automatic battery test, deep discharge protection, automatic recognition of extended battery modules (EBMs) |
Battery Type | 12V/9 Ah; sealed, lead-acid; maintenance free |
Battery Replacement | Hot-swappable internal batteries |
Start On Battery | Allows start of UPS without utility power |
Communications | |
User Interface | LCD graphical display |
LEDs | Load protected, on battery and fault |
Communication Ports | 1 USB HID compliant port + 1 RS232 serial port and relay contacts (USB and RS232 ports cannot be used simultaneously) |
Communications Card Slots | 1 slot for ConnectUPS-MS network management card |
Power Management Software | Eaton Intelligent Power Software Suite CD (included) |
Environmental & Standards | |
Heat Dissipation (BTU) | Line: 305, Battery: 2047 |
Audible Noise | 45 dBA |
Operating Temperature | 0°C to 40°C (32°F to 104°F) |
Performance - Safety - EMC | UL1778; UL497A; cUL |
Safety markings | UL, cUL |
EMC Markings | FCC Part 15 subpart B Class A |
Storage Temperature | -15°C–50°C (5°F–122°F) |
Relative Humidity | 20–95% non-condensing |
Altitude | Up to 10,000 ft (3000m) without de-rating |